(Click on thumbnail to enlarge)

T-Links Series Self Regulating Heating Cable
Download Data Sheet
Request Information or Quote

Performance Ratings

Output wattage:
3, 5, 8, 10 w/ft at 50°F (10°C)
9, 15, 26, 32 w/meter

Supply Voltage:
110 – 120 or 208V – 277Vac
Continuous maintenance temperature:
150°F (65°C)

Maximum exposure temperature:
185°F (85°C)

Approvals/Certifications
T-Links
120 Volts, 240 Volts
3 ,5, 8,10 Watts/Ft @ 50°F
Listed:
Pipe Heating Cable, Industrial and
Commercial
De-Icing and Snowmelting
Equipment

Description

The T-Link series of self-regulating heating cable is manufactured to supply a specified amount of heat at any point along its length in direct response to local temperature/thermo-dynamic variations. These Heat Trace Products, LLC. cables can be used to simplify the installation of heat tracing systems. T-Link heating cable runs are preterminated for ease of connectivity and installation. All components in the system are waterproof to insure long life at connection and termination points.

View the T-Link Heating Cable Brochure

120 Volt Breaker Sizing vs. Max Circuit length (FT)

Power Output Curves T-Links Series
15A20A30A40A
2703-1 If started at: 50°F 0°F -20°F300 200 180- 270 230- 330 330- - -
2705-1 If started at: 50°F 0°F -20°F230 150 130270 200 175- 270 260- - 270
2708-1 If started at: 50°F 0°F -20°F150 95 85200 125 100210 190 170- 210 210
2710-1 If started at: 50°F 0°F -20°F115 70 60150 95 85180 145 120- 180 165

240 Volt Breaker Sizing vs. Max Circuit Length (FT)

Product Ordering Information
15A20A30A40A
2703-2 If started at: 50°F 0°F -20°F660 410 360- 560 480- 660 660- - -
2705-2 If started at: 50°F 0°F -20°F400 300 260540 400 345- 540 520- - 540
2708-2 If started at: 50°F 0°F -20°F295 195 170390 250 225420 375 340- 420 420
2710-2 If started at: 50°F 0°F -20°F230 150 130305 200 175360 300 260- 360 360