Cable Selection Guide
Self-Regulating Heating Cable
| HEATING CABLE | FM APPROVALS | ||||||||||
| Series | Maintenance Temperature °F |
Ordinary Area | Class I | Class II | Class III | Zone 1* | Zone 2 | ||||
| Div 1* | Div 2 | Div 1* | Div 2 | Div 1* | Div 2 | ||||||
| Continuous | Intermittent | Groups | |||||||||
| 2000 | 385 | 450 | Yes | B,C,D | A,B,C,D | E,F,G | F,G | E,F,G | E,F,G | IIB+H | IIC |
| 2300 | 250 | 366 | Yes | B,C,D | B,C,D | F,G | Yes | ||||
| 2700 | 150 | 185 | Yes | B,C,D | B,C,D | F,G | Yes | Yes | |||
| 2800 | 150 | 185 | |||||||||
| HEATING CABLE | CSA APPROVALS | UL | SEMKO | ||||||||
| Series | T Rating** | Available Watt/ft |
Ordinary Area |
Class I | Class II | Class III | Ordinary Area |
CE Mark | |||
| Div 1* | Div 2 | Div 1* | Div 2 | Div 1* | Div 2 | ||||||
| Groups | |||||||||||
| 2000 | T-2C | 5 to 30 | 3(A,B,C), 5(A,B) | A,B,C,D | A,B,C,D | E,F,G | E,F,G | Yes | Yes | Yes | |
| 2300 | T-3 | 5 to 15 | 3(A,B,C), 5(A,B) | A,B,C,D | A,B,C,D | E,F,G | E,F,G | Yes | Yes | Pipe Heating Cable | Yes |
| 2700 | T-5, T-6 | 3 to 10 | 2E, 3(A,B,C), 5(A,B) | A,B,C,D | A,B,C,D | E,F,G | E,F,G | Yes | Yes | Pipe Heating Cable*** Roof & Gutter De-Icing |
Yes |
| 2800 | 3 to 6 | 2E, 3(A,B,C) | Pipe Heating Cable | Yes | |||||||
* Contact Heat Trace Products representative for information on Division I hazardous location systems
** T Rating per the 1999 NEC, Tables 500-5(d) and verified by FM
*** This heating cable can also be used for Hot Water Maintenance applications
The material contained in this document is presented in good faith and believed to be reliable and accurate. However, because testing conditions may vary and material quality or information that may be provided in whole or in part by others may be beyond our control, no warranty expressed or implied, is given and Heat Trace Products can assume no liability for results obtained or damages incurred through the application of the data and tests presented.